Geomembrane Liner Installation Guide

‌I. Pre-Installation Preparation‌

‌1. Surface Preparation

  • Compact subgrade to ≥90% Proctor density
  • Remove all debris >20mm (stones, metal objects)
  • Excavate 40cm×40cm anchor trenches along perimeter

‌II. Deployment Procedures‌

‌1. Layout & Cutting‌

  • Unroll geomembrane on clean area
  • Cut to designed shapes with 1-4% slack allowance

‌2. Placement Protocol

  • Minimize seams using T-seam pattern
  • Secure exposed edges immediately with sandbags
  • Maintain wrinkle-free placement

‌3. Weather Constraints

‌Parameter‌‌Allowable Range‌
Temperature4°C – 40°C
PrecipitationNone (surface dry)
Wind Speed≤4.5 m/s (≤16 km/h)

‌

Geomembrane Liner Installation Guide
Geomembrane Liner Installation Guide

III. Welding Specifications

‌1. Thermal Fusion Welding

  • 15cm overlap minimum
  • Pre-clean surfaces with approved solvents

‌2. Extrusion Welding

  • 7.5cm overlap minimum
  • Bevel edges at 45° (0.5mm depth)
  • Use virgin resin welding rods

‌3. Slope Welding Technique‌

  1. Weld vertically down slopes
  2. Anchor membrane at platforms
  3. Post-weld sandbag anchoring

‌IV. Critical Quality Control‌

‌1. Defect Repair Protocol

  • ≤6mm holes: Extrusion repair
  • 6mm holes: Circular patch (min. 15cm overlap)
  • All repairs require nondestructive testing (NDT)

‌2. Anchoring Requirements

  • U-shaped trench configuration
  • Secure with sandbags or concrete

‌3. Protection Measures‌

  • Install geotextile cushion layer immediately
  • Cover with granular fill or concrete

‌Safety & Compliance Directives‌

  1. ‌Access Control‌: Permit-only personnel in work zones
  2. ‌Footwear‌: Non-spiked shoes mandatory
  3. ‌Material Handling‌: No dragging/dropping of rolls
  4. ‌Welding QC‌:
    • Continuous speed monitoring
    • Destructive testing every 500m

Key Technical Terms: HDPE geomembrane, thermal fusion welding, extrusion welding, nondestructive testing (NDT), anchor trench